Reduction of air pollutant concentrations in an indoor ice-skating rink
AbstractHigh carbon monoxide and nitrogen dioxide concentrations were measured in an indoor ice-skating rink with fuel-powered ice-resurfacing equipment. In 22% to 33% of the measurements over 90-min segments, CO concentrations exceeded 20 μL/L as a 90-min average in the absence of rink ventilation. Average NO2 concentrations over 14 h were higher than 600 nL/L. Reduction of air pollutant concentrations in the ice-skating rink is necessary to prevent air-pollutant-exposure-related health incidents. Various methods for reducing air pollutants in an ice-skating rink were evaluated by simultaneously measuring CO and NO2 concentrations. Single pollution reduction attempts, such as extension of the exhaust pipe, reduction in the number of resurfacer operations, or use of an air recirculation system, did not significantly reduce air pollutant concentrations in the rink. Full operation of the mechanical ventilation system combined with reduced resurfacer operation was required to keep the air pollutant levels in the skating rink below the recommended guidelines. This investigation showed that management of clean air quality in an ice-skating rink is practically difficult as long as fuel-powered resurfacing equipment is used.
Reduction of air pollutant concentrations in an indoor ice-skating rink
AbstractHigh carbon monoxide and nitrogen dioxide concentrations were measured in an indoor ice-skating rink with fuel-powered ice-resurfacing equipment. In 22% to 33% of the measurements over 90-min segments, CO concentrations exceeded 20 μL/L as a 90-min average in the absence of rink ventilation. Average NO2 concentrations over 14 h were higher than 600 nL/L. Reduction of air pollutant concentrations in the ice-skating rink is necessary to prevent air-pollutant-exposure-related health incidents. Various methods for reducing air pollutants in an ice-skating rink were evaluated by simultaneously measuring CO and NO2 concentrations. Single pollution reduction attempts, such as extension of the exhaust pipe, reduction in the number of resurfacer operations, or use of an air recirculation system, did not significantly reduce air pollutant concentrations in the rink. Full operation of the mechanical ventilation system combined with reduced resurfacer operation was required to keep the air pollutant levels in the skating rink below the recommended guidelines. This investigation showed that management of clean air quality in an ice-skating rink is practically difficult as long as fuel-powered resurfacing equipment is used.
Reduction of air pollutant concentrations in an indoor ice-skating rink
Lee, Kiyoung (Autor:in) / Yanagisawa, Yukio (Autor:in) / Spengler, John D. (Autor:in)
Environmental International ; 20 ; 191-199
01.12.1993
9 pages
Aufsatz (Zeitschrift)
Elektronische Ressource
Englisch
Reduction of air pollutant concentrations in an indoor ice-skating rink
Online Contents | 1994
|Engineering Index Backfile | 1946
|Condensation risk assessment for an indoor ice skating rink
British Library Online Contents | 1996
|Engineering Index Backfile | 1931