Multi-criteria numerical analysis of factors influencing the efficiency of natural smoke venting of atria
AbstractSmoke management in the atrium with natural smoke venting is influenced by many parameters. The analysis presented considered the impact of atrium height, atrium shape and layout of air inlets, wind direction, wind speed and location of the fire outbreak. Experimental research is here very awkward due to the costs, thus the numerical analysis is a convenient way to examine such a large parameters domain. So wide range of research was feasible thanks to the use of Taguchi method of experiment design. The flow volume through the exhaust vents and the soot mass fraction at the ground floor were chosen as criteria to evaluate the efficiency of the smoke removal system As a result, the relative importance of examined parameters were obtained, and above all the interactions between parameters were revealed. This allows to formulate some hints for designers to make the smoke removal systems robust on the wind influence and other unpredictable factors.
HighlightsMany parameters influencing the efficiency of the smoke removal system was examined.The CFD methods were used to resolve the atrium models.Taguchi method of the experiment design was applied to make the task feasible.The relative importance of examined parameters were obtained.The applied tool allowed also to reveal interactions between parameters.
Multi-criteria numerical analysis of factors influencing the efficiency of natural smoke venting of atria
AbstractSmoke management in the atrium with natural smoke venting is influenced by many parameters. The analysis presented considered the impact of atrium height, atrium shape and layout of air inlets, wind direction, wind speed and location of the fire outbreak. Experimental research is here very awkward due to the costs, thus the numerical analysis is a convenient way to examine such a large parameters domain. So wide range of research was feasible thanks to the use of Taguchi method of experiment design. The flow volume through the exhaust vents and the soot mass fraction at the ground floor were chosen as criteria to evaluate the efficiency of the smoke removal system As a result, the relative importance of examined parameters were obtained, and above all the interactions between parameters were revealed. This allows to formulate some hints for designers to make the smoke removal systems robust on the wind influence and other unpredictable factors.
HighlightsMany parameters influencing the efficiency of the smoke removal system was examined.The CFD methods were used to resolve the atrium models.Taguchi method of the experiment design was applied to make the task feasible.The relative importance of examined parameters were obtained.The applied tool allowed also to reveal interactions between parameters.
Multi-criteria numerical analysis of factors influencing the efficiency of natural smoke venting of atria
Król, Małgorzata (Autor:in) / Król, Aleksander (Autor:in)
Journal of Wind Engineering and Industrial Aerodynamics ; 170 ; 149-161
18.08.2017
13 pages
Aufsatz (Zeitschrift)
Elektronische Ressource
Englisch
Efficiency of Smoke Control of Atria by Natural Venting
British Library Conference Proceedings | 1992
|Efficiency of smoke control of atria by mechanical smoke venting
British Library Conference Proceedings | 1995
|Experimental Studies on Natural Smoke Filling in Atria
British Library Online Contents | 2000
|Experimental Studies on Natural Smoke Filling in Atria
Online Contents | 2000
|British Library Online Contents | 1999