Eine Plattform für die Wissenschaft: Bauingenieurwesen, Architektur und Urbanistik
Seattle Distribution System Corrosion Control Study. Volume 2. Tolt River Water Pilot Plant Study
For 6 months, the Seattle Water Department conducted a corrosion treatment pilot plant study, obtaining data on the treatment of Tolt River water with lime/sodium carbonate, lime/sodium bicarbonate, and lime/bicarbonate/silicate. Continuous-flow pipe coupon tests were conducted to determine corrosion rates, penetration rates, and corrosion types for copper, galvanized steel and black steel pipes. Metal leaching tests were conducted using small diameter pipes. Research showed that using lime plus sodium carbonate, lime plus sodium bicarbonate, and lime plus bicarbonate plus silicate will significantly reduce corrosion in home plumbing systems. Based on this pilot study, lime plus sodium carbonate treatment is recommended for the Cedar River water supply at an average dosage of 1.7 mg/L CaO. This dose should achieve an average distribution system pH of 7.9 and an alkalinity of 18 mg/l CaCO3.
Seattle Distribution System Corrosion Control Study. Volume 2. Tolt River Water Pilot Plant Study
For 6 months, the Seattle Water Department conducted a corrosion treatment pilot plant study, obtaining data on the treatment of Tolt River water with lime/sodium carbonate, lime/sodium bicarbonate, and lime/bicarbonate/silicate. Continuous-flow pipe coupon tests were conducted to determine corrosion rates, penetration rates, and corrosion types for copper, galvanized steel and black steel pipes. Metal leaching tests were conducted using small diameter pipes. Research showed that using lime plus sodium carbonate, lime plus sodium bicarbonate, and lime plus bicarbonate plus silicate will significantly reduce corrosion in home plumbing systems. Based on this pilot study, lime plus sodium carbonate treatment is recommended for the Cedar River water supply at an average dosage of 1.7 mg/L CaO. This dose should achieve an average distribution system pH of 7.9 and an alkalinity of 18 mg/l CaCO3.
Seattle Distribution System Corrosion Control Study. Volume 2. Tolt River Water Pilot Plant Study
C. E. Herrera (Autor:in) / B. P. Hoyt (Autor:in)
1984
111 pages
Report
Keine Angabe
Englisch
Civil Engineering , Corrosion & Corrosion Inhibition , Corrosion prevention , Distribution systems , Plumbing , Water treatment , Tolt River , Pilot plants , Penetration , Sodium carbonates , Calcium oxides , Bicarbonates , Protection , Steels , Lead(Metal) , Zinc , Copper , Dosage , Cedar River , Water supply , Washington(State) , Graphs(Charts) , Photographs
Tolt River Water Treatment Project
Springer Verlag | 2002
|Automatisiertes Ueberwachungssystem am Tolt-Staudamm bei Seattle, USA
British Library Online Contents | 1998
|Tolt Dam Failure Warning System
British Library Conference Proceedings | 1993
|Tolt dam monitoring and failure warning system
Tema Archiv | 2009
|