Eine Plattform für die Wissenschaft: Bauingenieurwesen, Architektur und Urbanistik
Internal-corrosion inhibitors for pipelines carrying deaerated heating water
Abstract The effect of internal-corrosion inhibitors on heating-system pipelines is investigated. Tests were conducted on a testing device for polarization measurements under conditions corresponding to the Rostov Heat-Supply System. The concentration of OEDP-zinc, which provides a high degree of protection from general corrosion, is determined. The reagent has been successfully incorporated into the Rostov No. 2 TPP.
Internal-corrosion inhibitors for pipelines carrying deaerated heating water
Abstract The effect of internal-corrosion inhibitors on heating-system pipelines is investigated. Tests were conducted on a testing device for polarization measurements under conditions corresponding to the Rostov Heat-Supply System. The concentration of OEDP-zinc, which provides a high degree of protection from general corrosion, is determined. The reagent has been successfully incorporated into the Rostov No. 2 TPP.
Internal-corrosion inhibitors for pipelines carrying deaerated heating water
Balaban-Irmenin, Yu. V. (Autor:in) / Fokina, N. G. (Autor:in)
2007
Aufsatz (Zeitschrift)
Englisch
Internal-corrosion inhibitors for pipelines carrying deaerated heating water
Springer Verlag | 2007
|Continuous monitoring of aluminum corrosion process in deaerated water
British Library Online Contents | 2007
|The absorption of oxygen by deaerated water
Engineering Index Backfile | 1913
|