Details of reinforcement of autoclaved aerated concrete lintels for shear and anchorage
Abstract This paper is a study of the shear capacity of autoclaved aerated concrete lintels reinforced with unbonded bars. A set of tests was performed to measure the anchorage capacity of the beam ends with seven different configurations. Full lintels were also tested to failure under transverse loading for two steel details. The study of the test results confirms that the lintels fail in a brittle mode when the anchorage capacity of the longitudinal bars is reached. A steel detail producing a stiff truss action at the beam ends relieving the stresses on the concrete shows to be the best arrangement, increasing the strength of the beams and producing a relatively ductile failure.
Résumé Cet article concerne l'étude de la capacité en cisaillement de poutres en béton cellulaire autoclavé en l'absence d'adhérence entre l'armature et le béton. Une série d'essais a été menée pour mesurer la capacité d'ancrage à l'extrémité des poutres, utilisant sept configurations différentes d'armature. En complément, une série d'essais de surcharge latérale des poutres a été effectuée utilisant deux configurations d'armature. L'étude des résultats des essais confirme que la rupture des poutres est fragile quand la capacité d'ancrage des armatures longitudinales est atteinte. La configuration d'armatures en forme de treillis rigide aux extrémités de la poutre, diminuant ainsi la contrainte du béton, s'avère la meilleure disposition pour augmenter la résistance de la poutre tout en augmentant sa ductilité.
Details of reinforcement of autoclaved aerated concrete lintels for shear and anchorage
Abstract This paper is a study of the shear capacity of autoclaved aerated concrete lintels reinforced with unbonded bars. A set of tests was performed to measure the anchorage capacity of the beam ends with seven different configurations. Full lintels were also tested to failure under transverse loading for two steel details. The study of the test results confirms that the lintels fail in a brittle mode when the anchorage capacity of the longitudinal bars is reached. A steel detail producing a stiff truss action at the beam ends relieving the stresses on the concrete shows to be the best arrangement, increasing the strength of the beams and producing a relatively ductile failure.
Résumé Cet article concerne l'étude de la capacité en cisaillement de poutres en béton cellulaire autoclavé en l'absence d'adhérence entre l'armature et le béton. Une série d'essais a été menée pour mesurer la capacité d'ancrage à l'extrémité des poutres, utilisant sept configurations différentes d'armature. En complément, une série d'essais de surcharge latérale des poutres a été effectuée utilisant deux configurations d'armature. L'étude des résultats des essais confirme que la rupture des poutres est fragile quand la capacité d'ancrage des armatures longitudinales est atteinte. La configuration d'armatures en forme de treillis rigide aux extrémités de la poutre, diminuant ainsi la contrainte du béton, s'avère la meilleure disposition pour augmenter la résistance de la poutre tout en augmentant sa ductilité.
Details of reinforcement of autoclaved aerated concrete lintels for shear and anchorage
Kuenen, K. (Autor:in) / Boutros, M. (Autor:in)
Materials and Structures ; 31 ; 536-542
01.10.1998
7 pages
Aufsatz (Zeitschrift)
Elektronische Ressource
Englisch
Details of reinforcement of autoclaved aerated concrete lintels for shear and anchorage
Online Contents | 1998
|Details of reinforcement of autoclaved aerated concrete lintels for shear and anchorage
British Library Online Contents | 1998
|Anchorage capacity of reinforcing bars in autoclaved aerated concrete lintels
Online Contents | 1997
|Anchorage Capacity of Reinforcing Balls in Autoclaved Aerated Concrete Lintels
British Library Online Contents | 1997
|