Corrosion of stainless steel piping in high manganese fresh water
A potable water treatment plant, designed to reduce manganese and iron in well water, experienced leaks in the 16 in. (406 mm) raw water header about nine months after startup. The material, type 304 (UNS 30403) stainless steel, was purchased to American Society of Testing Materials specification A 778, with additional stupilations governing internal finish, the use of filler metal, and pickling for scale removal. Laboratory screenings of deposits for bacteria revealed some potentially additive corrosive effects from microbial action. However, the correlation of corrosion with the presence or absence of heat tint in the heat-affected zone of the circumferential welds prevailed as a primary cause of the corrosion observed beneath an adherent manganese-iron deposit in a low chloride, high manganese, raw water.
Corrosion of stainless steel piping in high manganese fresh water
A potable water treatment plant, designed to reduce manganese and iron in well water, experienced leaks in the 16 in. (406 mm) raw water header about nine months after startup. The material, type 304 (UNS 30403) stainless steel, was purchased to American Society of Testing Materials specification A 778, with additional stupilations governing internal finish, the use of filler metal, and pickling for scale removal. Laboratory screenings of deposits for bacteria revealed some potentially additive corrosive effects from microbial action. However, the correlation of corrosion with the presence or absence of heat tint in the heat-affected zone of the circumferential welds prevailed as a primary cause of the corrosion observed beneath an adherent manganese-iron deposit in a low chloride, high manganese, raw water.
Corrosion of stainless steel piping in high manganese fresh water
Korrosion von Rohrleitungen aus nichtrostendem Stahl durch Frischwasser mit hohem Mangangehalt
Avery, R.E. (Autor:in) / Lutey, R.W. (Autor:in) / Musick, J. (Autor:in) / Pinnow, K.E. (Autor:in) / Tuthill, A.H. (Autor:in)
Materials Performance ; 35 ; 59-62
1996
4 Seiten, 4 Bilder, 1 Tabelle, 2 Quellen
Aufsatz (Zeitschrift)
Englisch
Corrosion of Stainless Steel Piping in High Manganese Fresh Water
British Library Online Contents | 1996
|Wiley | 1994
|Corrosion Resistance of Stainless Chromium - Manganese High Nitrogen Steel
British Library Online Contents | 2003
|Corrosion of Type 316L Stainless Steel Piping in Synthetic Gas Plants
British Library Online Contents | 2013
|Internal corrosion of steel piping in water mains
Tema Archiv | 1981
|