Insulated cross connections stop pipe electrolysis
Steel crossovers between first and second Mokelumne aqueducts had caused leaks to develop rapidly on older aqueduct, even though it had been under cathodic protection for 15 yr; as result of survey with recording potentiometer, two aqueducts were isolated from each other by installing insulated joints in cross connection; since this was done, there have been no further leaks.
Insulated cross connections stop pipe electrolysis
Steel crossovers between first and second Mokelumne aqueducts had caused leaks to develop rapidly on older aqueduct, even though it had been under cathodic protection for 15 yr; as result of survey with recording potentiometer, two aqueducts were isolated from each other by installing insulated joints in cross connection; since this was done, there have been no further leaks.
Insulated cross connections stop pipe electrolysis
Water Works Eng