Fire resilience of composite beams with simple connections: Parametric studies and design
AbstractSimple (shear) connections are designed to resist vertical shear forces resulting from gravity loading. During a fire event, floor systems expand and rotate, imposing axial forces (compressive and tensile) on simple connections. This paper presents the results of analytical parametric studies conducted to expand the experimental database and evaluate the structural response of composite beams with simple connections subjected to combined gravity loads and design fire scenarios. The parametric studies were conducted using 3D finite element models of partial frame assemblies consisting of composite beams with simple connections. These models were developed and benchmarked previously by the authors [1] using experimental data [2, 3]. These models explicitly accounted for the effects of geometric and material nonlinearity including concrete cracking and crushing, steel yielding and fracture, and the interaction between various structural components. The parameters included in the analytical studies were the connection type (shear-tab, single-angle, double-angle), deck type (flat slab, perpendicular metal deck), composite slab continuity across multiple bays, slab reinforcement type (wire mesh, mild steel), fire resistance rating of the design, and the design fire scenario (1hour fire with cooling, 2hour fire with cooling, E119). The results from the parametric studies indicated that for typical composite beams and simple connections designed with certain (n-hour) fire resistance rating, and subjected to design fire scenario with the same (n-hour) heating followed by cooling, there was no premature fracture failure of the connection leading to collapse of the composite beams. The continuity of composite slab across bays and the steel reinforcement has a significant influence on the performance of the simple connections, and the resilience of the composite beam system.
HighlightsComposite beams protected with 1h FRR and subjected to a 1h fire have damage in the connection during coolingComposite beams protected with 2h FRR have no damage or failure when subjected to a 2h design fireConsideration of slab continuity will improve the behavior of composite beams in fire conditionsMild steel reinforcement in the slab will improve the behavior of composite beams in fire conditions
Fire resilience of composite beams with simple connections: Parametric studies and design
AbstractSimple (shear) connections are designed to resist vertical shear forces resulting from gravity loading. During a fire event, floor systems expand and rotate, imposing axial forces (compressive and tensile) on simple connections. This paper presents the results of analytical parametric studies conducted to expand the experimental database and evaluate the structural response of composite beams with simple connections subjected to combined gravity loads and design fire scenarios. The parametric studies were conducted using 3D finite element models of partial frame assemblies consisting of composite beams with simple connections. These models were developed and benchmarked previously by the authors [1] using experimental data [2, 3]. These models explicitly accounted for the effects of geometric and material nonlinearity including concrete cracking and crushing, steel yielding and fracture, and the interaction between various structural components. The parameters included in the analytical studies were the connection type (shear-tab, single-angle, double-angle), deck type (flat slab, perpendicular metal deck), composite slab continuity across multiple bays, slab reinforcement type (wire mesh, mild steel), fire resistance rating of the design, and the design fire scenario (1hour fire with cooling, 2hour fire with cooling, E119). The results from the parametric studies indicated that for typical composite beams and simple connections designed with certain (n-hour) fire resistance rating, and subjected to design fire scenario with the same (n-hour) heating followed by cooling, there was no premature fracture failure of the connection leading to collapse of the composite beams. The continuity of composite slab across bays and the steel reinforcement has a significant influence on the performance of the simple connections, and the resilience of the composite beam system.
HighlightsComposite beams protected with 1h FRR and subjected to a 1h fire have damage in the connection during coolingComposite beams protected with 2h FRR have no damage or failure when subjected to a 2h design fireConsideration of slab continuity will improve the behavior of composite beams in fire conditionsMild steel reinforcement in the slab will improve the behavior of composite beams in fire conditions
Fire resilience of composite beams with simple connections: Parametric studies and design
Ph.D., P.E. Fischer, Erica C. (author) / Ph.D. Varma, Amit H. (author)
Journal of Constructional Steel Research ; 128 ; 119-135
2016-08-05
17 pages
Article (Journal)
Electronic Resource
English
Fire resilience of composite beams with simple connections: Parametric studies and design
Online Contents | 2017
|Fire behavior of composite beams with simple connections: Benchmarking of numerical models
Online Contents | 2015
|Fire behavior of composite beams with simple connections: Benchmarking of numerical models
British Library Online Contents | 2015
|Fire resilience of shear connections in a composite floor: Numerical investigation
British Library Online Contents | 2016
|