Flexural behavior of fire-damaged reinforced concrete beams repaired with high-strength fiber reinforced mortar
The purpose of this study is to investigate the effect on flexural strength of fire-damaged concrete repaired with high-strength mortar (HSM).
Reinforced concrete beams with dimension of 100 mm × 100 mm × 500 mm were used in this study. Beams were then heated to 400°C and overlaid with either HSM or high-strength fiber reinforced mortar (HSFM) to measure the effectiveness of repair material. Repaired beams of different material were then tested for flexural strength. Another group of beams was also repaired and tested by the same procedure but was heated at higher temperature of 600°C.
Repair of 400°C fire-damaged samples using HSM regained 72 per cent of its original flexural strength, 100.8 per cent of its original toughness and 56.9 per cent of its original elastic stiffness. Repair of 400°C fire-damaged samples using HSFM regained 113.5 per cent of its original flexural strength, 113 per cent of its original toughness and 85.1 per cent of its original elastic stiffness. Repair of 600°C fire-damaged samples using HSM regained 18.7 per cent of its original flexural strength, 25.9 per cent of its original peak load capacity, 26.1 per cent of its original toughness and 22 per cent of its original elastic stiffness. Repair of 600°C fire-damaged samples using HSFM regained 68.4 per cent of its original flexural strength, 96.5 per cent of its original peak load capacity, 71.2 per cent of its original toughness and 52.2 per cent of its original elastic stiffness.
This research is limited to the size of the furnace. The beam specimen is limited to 500 mm of length and overall dimensions. This dimension is not practical in actual structure, hence it may cause exaggeration of deteriorating effect of heating on reinforced concrete beam.
This study may promote more investigation of using HSM as repair material for fire-damaged concrete. This will lead to real-world application and practical solution for fire-damaged structure.
The aim of this research in using HSM mostly due to the material’s high workability which will ease its application and promote quality in repair of damaged structure.
There is a dearth of research on using HSM as repair material for fire-damaged concrete. Some research has been carried out using mortar but at lower strength compared to this research.
Flexural behavior of fire-damaged reinforced concrete beams repaired with high-strength fiber reinforced mortar
The purpose of this study is to investigate the effect on flexural strength of fire-damaged concrete repaired with high-strength mortar (HSM).
Reinforced concrete beams with dimension of 100 mm × 100 mm × 500 mm were used in this study. Beams were then heated to 400°C and overlaid with either HSM or high-strength fiber reinforced mortar (HSFM) to measure the effectiveness of repair material. Repaired beams of different material were then tested for flexural strength. Another group of beams was also repaired and tested by the same procedure but was heated at higher temperature of 600°C.
Repair of 400°C fire-damaged samples using HSM regained 72 per cent of its original flexural strength, 100.8 per cent of its original toughness and 56.9 per cent of its original elastic stiffness. Repair of 400°C fire-damaged samples using HSFM regained 113.5 per cent of its original flexural strength, 113 per cent of its original toughness and 85.1 per cent of its original elastic stiffness. Repair of 600°C fire-damaged samples using HSM regained 18.7 per cent of its original flexural strength, 25.9 per cent of its original peak load capacity, 26.1 per cent of its original toughness and 22 per cent of its original elastic stiffness. Repair of 600°C fire-damaged samples using HSFM regained 68.4 per cent of its original flexural strength, 96.5 per cent of its original peak load capacity, 71.2 per cent of its original toughness and 52.2 per cent of its original elastic stiffness.
This research is limited to the size of the furnace. The beam specimen is limited to 500 mm of length and overall dimensions. This dimension is not practical in actual structure, hence it may cause exaggeration of deteriorating effect of heating on reinforced concrete beam.
This study may promote more investigation of using HSM as repair material for fire-damaged concrete. This will lead to real-world application and practical solution for fire-damaged structure.
The aim of this research in using HSM mostly due to the material’s high workability which will ease its application and promote quality in repair of damaged structure.
There is a dearth of research on using HSM as repair material for fire-damaged concrete. Some research has been carried out using mortar but at lower strength compared to this research.
Flexural behavior of fire-damaged reinforced concrete beams repaired with high-strength fiber reinforced mortar
Abdullah, Muhd Afiq Hizami (author) / Mohd Zahid, Mohd Zulham Affandi (author) / Ayob, Afizah (author) / Muhamad, Khairunnisa (author)
Journal of Structural Fire Engineering ; 10 ; 56-75
2019-02-28
1 pages
Article (Journal)
Electronic Resource
English
British Library Online Contents | 2016
|British Library Online Contents | 2016
|Flexural performance of reinforced concrete beams repaired with fiber-reinforced SCC
Tema Archive | 2007
|Flexural performance of reinforced concrete beams repaired with fiber-reinforced SCC
British Library Conference Proceedings | 2007
|