LOFT Diesel Generator ''A'' Exhaust Stack Seismic Analysis
A stress analysis of the LOFT Diesel Generator ''A'' Exhaust Stack was performed to determine its reaction to Safe-Shutdown Earthquake loads. The exhaust stack silencer and supporting foundation was found to be inadequate for the postulated seismic accelerations. Lateral support is required to prevent overturning of the silencer pedestal and reinforcement of the 4'' x 0.5'' silencer base straps is necessary. Basic requirements for this additional support are discussed. (ERA citation 03:047830)
LOFT Diesel Generator ''A'' Exhaust Stack Seismic Analysis
A stress analysis of the LOFT Diesel Generator ''A'' Exhaust Stack was performed to determine its reaction to Safe-Shutdown Earthquake loads. The exhaust stack silencer and supporting foundation was found to be inadequate for the postulated seismic accelerations. Lateral support is required to prevent overturning of the silencer pedestal and reinforcement of the 4'' x 0.5'' silencer base straps is necessary. Basic requirements for this additional support are discussed. (ERA citation 03:047830)
LOFT Diesel Generator ''A'' Exhaust Stack Seismic Analysis
R. K. Blandford (author)
1978
29 pages
Report
No indication
English
Review of Initial Steam Generator Analysis- Loft Program
NTIS | 1967
|LOFT 3C Cable Tray and Ladder Seismic Analysis
NTIS | 1979
|LOFT Steam Generator Thermal Analysis Class I Review
NTIS | 1977
|Seismic upgrade design for an exhaust stack building
NTIS | 1991
|