A platform for research: civil engineering, architecture and urbanism
Fire Experiments of Zoned Smoke Control at the Plaza Hotel in Washington DC
A series of full-scale tests were conducted to evaluate the current approach to zoned smoke control systems with and without stairwell pressurization. Smoke movement and the performance of smoke control systems were studied with smoke generated from unsprinklered wood fires, sprinklered wood fires, and smoke bombs. As expected, the zoned smoke control system prevented smoke migration beyond the fire floor. The minimum pressure difference approach to achieve smoke control for zoned smoke control systems was evaluated. The minimum pressure difference approach is based on a tacit assumption of a constant mass flow rate into the zone where the fire is located. To evaluate the assumption, a model was developed for mass flow in the smoke zone. Agreement between experimental results and calculations based on the model was good.
Fire Experiments of Zoned Smoke Control at the Plaza Hotel in Washington DC
A series of full-scale tests were conducted to evaluate the current approach to zoned smoke control systems with and without stairwell pressurization. Smoke movement and the performance of smoke control systems were studied with smoke generated from unsprinklered wood fires, sprinklered wood fires, and smoke bombs. As expected, the zoned smoke control system prevented smoke migration beyond the fire floor. The minimum pressure difference approach to achieve smoke control for zoned smoke control systems was evaluated. The minimum pressure difference approach is based on a tacit assumption of a constant mass flow rate into the zone where the fire is located. To evaluate the assumption, a model was developed for mass flow in the smoke zone. Agreement between experimental results and calculations based on the model was good.
Fire Experiments of Zoned Smoke Control at the Plaza Hotel in Washington DC
J. H. Klote (author)
1990
76 pages
Report
No indication
English
Architectural Design & Environmental Engineering , Construction Materials, Components, & Equipment , Fire tests , Hotels , Fire protection , Smoke , Ventilation , Residential buildings , Fire safety , Fires , Combustion products , Air circulation , Air flow , Mathematical models , Temperature , Experimental data , Pressure gradients
Fire Experiments of Zoned Smoke Control at the Plaza Hotel in Washington, D.C. (RP-504)
British Library Conference Proceedings | 1990
|Zoned Smoke Control Applications
British Library Online Contents | 1998
|Full scale smoke control tests at the Plaza Hotel building
Tema Archive | 1989
|Fire and Smoke Spread Dynamics in the Dupont Plaza Hotel Fire on December 31, 1986
British Library Conference Proceedings | 1995
|Online Contents | 2008
|