CRREL Roof Moisture Survey. Pease AFB Buildings 33, 116, 122 and 205
Four building roofs at Pease AFB were surveyed with a hand-held infrared camera to detect wet insulation. Areas of wet insulation on these roofs were marked with spray paint, and 3-in.-diam core samples of the built-up membrane and insulation were taken to verify wet and dry conditions. Flashing defects are considered responsible for most of the wet insulation uncovered in this survey. Recommendations for maintenance, repair, and replacement were developed from the infrared surveys, core samples and visual examinations. (Author)
CRREL Roof Moisture Survey. Pease AFB Buildings 33, 116, 122 and 205
Four building roofs at Pease AFB were surveyed with a hand-held infrared camera to detect wet insulation. Areas of wet insulation on these roofs were marked with spray paint, and 3-in.-diam core samples of the built-up membrane and insulation were taken to verify wet and dry conditions. Flashing defects are considered responsible for most of the wet insulation uncovered in this survey. Recommendations for maintenance, repair, and replacement were developed from the infrared surveys, core samples and visual examinations. (Author)