Indoor air distribution in a room with underfloor air distribution and chilled ceiling: Effect of ceiling surface temperature and supply air velocity
An underfloor air distribution (UFAD) system integrated with a chilled ceiling (CC) cooling system may be a potential advanced heating, ventilation and air conditioning system in modern non-residential buildings with high sensible cooling loads. This article presents an experimental study concerning the effect of ceiling surface temperature and supply air velocity on the indoor air distribution in a room with UFAD as the internal and external sensible cooling loads change. The vertical distributions of indoor air temperature, air velocity and contaminant (CO2) concentration were evaluated by vertical air temperature difference (VATD), turbulence intensity (TI) and contaminant removal effectiveness (CRE), respectively. The results showed that the average VATD, TI and CRE levels were 0.5°C–1.0°C, 31%–41% and 0.85–1.06 when both internal and external sensible cooling loads were 41.5 W/m2. These evaluation indices varied clearly when the external sensible cooling load increased from 41.5 W/m2 to 69.5 W/m2, whereas they remained almost the same when the internal sensible cooling load increased from 41.5 W/m2 to 69.5 W/m2. The maximum TI coincided with the minimum CRE under the condition of a constant sensible cooling load. Moreover, an air diffusion performance index clearly reduced with an increase in the heat removal effectiveness. It is recommended that it is important to balance the indoor air quality and energy consumption in a room with UFAD + CC.
Indoor air distribution in a room with underfloor air distribution and chilled ceiling: Effect of ceiling surface temperature and supply air velocity
An underfloor air distribution (UFAD) system integrated with a chilled ceiling (CC) cooling system may be a potential advanced heating, ventilation and air conditioning system in modern non-residential buildings with high sensible cooling loads. This article presents an experimental study concerning the effect of ceiling surface temperature and supply air velocity on the indoor air distribution in a room with UFAD as the internal and external sensible cooling loads change. The vertical distributions of indoor air temperature, air velocity and contaminant (CO2) concentration were evaluated by vertical air temperature difference (VATD), turbulence intensity (TI) and contaminant removal effectiveness (CRE), respectively. The results showed that the average VATD, TI and CRE levels were 0.5°C–1.0°C, 31%–41% and 0.85–1.06 when both internal and external sensible cooling loads were 41.5 W/m2. These evaluation indices varied clearly when the external sensible cooling load increased from 41.5 W/m2 to 69.5 W/m2, whereas they remained almost the same when the internal sensible cooling load increased from 41.5 W/m2 to 69.5 W/m2. The maximum TI coincided with the minimum CRE under the condition of a constant sensible cooling load. Moreover, an air diffusion performance index clearly reduced with an increase in the heat removal effectiveness. It is recommended that it is important to balance the indoor air quality and energy consumption in a room with UFAD + CC.
Indoor air distribution in a room with underfloor air distribution and chilled ceiling: Effect of ceiling surface temperature and supply air velocity
Gao, Jie (author) / Wang, Haichao (author) / Wu, Xiaozhou (author) / Wang, Fenghao (author) / Tian, Zhen (author)
Indoor and Built Environment ; 29 ; 151-162
2020-02-01
12 pages
Article (Journal)
Electronic Resource
English
Impact of chilled ceiling in a high sensible cooling load room with underfloor air distribution