Shaking Table Test of Water Supply Pipes Installed in a Full-Scale Masonry Structure
The seismic performance of indoor water supply pipes plays a significant role during earthquakes, and the failure of pipes causes severe economic losses and other disasters. This paper presents shaking table test research on water supply pipes installed in a full-scale masonry structure. Three different material pipes and three different material fillers were combined to evaluate the difference in seismic performance. In this study, normalized floor response spectra and pipe acceleration amplification factors obtained from experimental data were compared with code provisions. Spectrum analysis was used to evaluate the pipeline seismic response, and the results showed that the combination of pipes and fillers with similar material properties vibrated partially at multiple frequencies. In contrast, the combination of pipes and fillers with very different material properties only vibrated near the predominant structural period.
Shaking Table Test of Water Supply Pipes Installed in a Full-Scale Masonry Structure
The seismic performance of indoor water supply pipes plays a significant role during earthquakes, and the failure of pipes causes severe economic losses and other disasters. This paper presents shaking table test research on water supply pipes installed in a full-scale masonry structure. Three different material pipes and three different material fillers were combined to evaluate the difference in seismic performance. In this study, normalized floor response spectra and pipe acceleration amplification factors obtained from experimental data were compared with code provisions. Spectrum analysis was used to evaluate the pipeline seismic response, and the results showed that the combination of pipes and fillers with similar material properties vibrated partially at multiple frequencies. In contrast, the combination of pipes and fillers with very different material properties only vibrated near the predominant structural period.
Shaking Table Test of Water Supply Pipes Installed in a Full-Scale Masonry Structure
KSCE J Civ Eng
Wu, Houli (author) / Guo, Endong (author) / Sun, Dezhang (author) / Mao, Chenxi (author) / Zhang, Haoyu (author) / Liu, Zhibin (author)
KSCE Journal of Civil Engineering ; 26 ; 824-836
2022-02-01
13 pages
Article (Journal)
Electronic Resource
English
Shaking table test and numerical analyses of a full scale three-leaf masonry wall
BASE | 2023
|Shaking Table Test of a Strengthened Full-Scale Stone Masonry Building with Flexible Diaphragms
Taylor & Francis Verlag | 2014
|Shaking‐table tests of a full‐scale single‐story masonry veneer wood‐frame structure
Online Contents | 2011
|