A platform for research: civil engineering, architecture and urbanism
Mechanistic modeling of copper corrosions in data center environments
Air-side economizers are increasingly used to take advantage of “free-cooling” in data centers with the intent of reducing the carbon footprint of buildings. However, they can introduce outdoor pollutants to indoor environment of data centers and cause corrosion damage to the information technology equipment. To evaluate the reliability of information technology equipment under various thermal and air-pollution conditions, a mechanistic model based on multi-ion transport and chemical reactions was developed. The model was used to predict Cu corrosion caused by Cl2-containing pollutant mixtures. It also accounted for the effects of temperature (25 °C and 28 °C), relative humidity (50%, 75%, and 95%), and synergism. It also identified higher air temperature as a corrosion barrier and higher relative humidity as a corrosion accelerator, which agreed well with the experimental results. The average root mean square error of the prediction was 13.7 Å. The model can be used to evaluate the thermal guideline for data centers design and operation when Cl2 is present based on pre-established acceptable risk of corrosion in data centers’ environment.
Mechanistic modeling of copper corrosions in data center environments
Air-side economizers are increasingly used to take advantage of “free-cooling” in data centers with the intent of reducing the carbon footprint of buildings. However, they can introduce outdoor pollutants to indoor environment of data centers and cause corrosion damage to the information technology equipment. To evaluate the reliability of information technology equipment under various thermal and air-pollution conditions, a mechanistic model based on multi-ion transport and chemical reactions was developed. The model was used to predict Cu corrosion caused by Cl2-containing pollutant mixtures. It also accounted for the effects of temperature (25 °C and 28 °C), relative humidity (50%, 75%, and 95%), and synergism. It also identified higher air temperature as a corrosion barrier and higher relative humidity as a corrosion accelerator, which agreed well with the experimental results. The average root mean square error of the prediction was 13.7 Å. The model can be used to evaluate the thermal guideline for data centers design and operation when Cl2 is present based on pre-established acceptable risk of corrosion in data centers’ environment.
Mechanistic modeling of copper corrosions in data center environments
Build. Simul.
Zhang, Rui (author) / Zhang, Jianshun (author) / Schmidt, Roger (author) / Gilbert, Jeremy L. (author)
Building Simulation ; 17 ; 483-492
2024-03-01
10 pages
Article (Journal)
Electronic Resource
English
chloride pollutant mixture , copper corrosion model , data center , temperature , relative humidity , synergistic effect Engineering , Building Construction and Design , Engineering Thermodynamics, Heat and Mass Transfer , Atmospheric Protection/Air Quality Control/Air Pollution , Monitoring/Environmental Analysis
Mechanistic modeling of copper corrosions in data center environments
Springer Verlag | 2024
|Les corrosions des chaudieres a grande production
Engineering Index Backfile | 1933
|Pitting and Stress Corrosions of Aluminum Alloys; Correlation between Them
British Library Online Contents | 2001
|