A platform for research: civil engineering, architecture and urbanism
Attenuation measurements on high-voltage overhead line
Measurements are reported of frequency-dependent transmission characteristics of 110 kv overhead line with 240/40 (21,7 mm diam) ASC conductors in triangular configuration, during different stages of line construction; measurements permitted calculated transmission characteristics to be checked and corrected; results presented show that there exist appreciable differences in attenuation between line configuration symmetrical to earth, and line configuration unsymmetrical to earth; conclusions are drawn as to HF interference due to corona.
Attenuation measurements on high-voltage overhead line
Measurements are reported of frequency-dependent transmission characteristics of 110 kv overhead line with 240/40 (21,7 mm diam) ASC conductors in triangular configuration, during different stages of line construction; measurements permitted calculated transmission characteristics to be checked and corrected; results presented show that there exist appreciable differences in attenuation between line configuration symmetrical to earth, and line configuration unsymmetrical to earth; conclusions are drawn as to HF interference due to corona.
Attenuation measurements on high-voltage overhead line
Conference Int des Grands Reseaux Electriques a Haute Tension -- CR
Bartenstein, R. (author) / Schafer, E. (author) / Vogl, W. (author)
20th Conference Internationale des Grands Reseaux Electriques a Haute Tension ; 1964
1964
21 pages
Conference paper
English
© Metadata Copyright Elsevier B. V. All rights reserved.
Tower for supporting overhead line of extra-high voltage electric power transmission
European Patent Office | 2018
|Three-phase transposition design structure of high-voltage long-distance overhead transmission line
European Patent Office | 2023
|Maintenance of a High-Voltage Overhead Transmission Line: Sustainability and Noise Impact Assessment
DOAJ | 2018
|